Aluminum-Copper Conductor Low Power Cable
Power Cable
XLPE
Low Voltage
Underground
Aluminum-Copper Conductor XLPE Insulated Underground Power Cable
Certification Standards
ISO 9001
IEC
CE
Implementation Standards
- BS 6622
- BS 7835 (LSZH Version)
Product Introduction
Construction
- Conductor: Plain annealed copper or aluminium complying with IEC 60228/BS 6360. Copper conductors shall be stranded and aluminium conductors shall be either solid or stranded.
- Conductor Screen: Extruded layer of semi-conducting cross-linkable compound is applied over the conductor and shall cover the surface completely. The minimum thickness is 0.3mm and the maximum resistivity shall not exceed 500 Ohm-m at 90°C.
- Insulation: Cross-linked polyethylene compound XLPE (GP8) conforming to BS 7655-1.3 or EPR (GP7), conforming to BS 7655-1.2.
- Insulation Screen: Extruded layer of semi-conducting cross-linkable compound is applied over the insulation. The minimum thickness is 0.3 mm and the maximum resistivity is 500 Ohm-m at 90°C.
- Metallic Layer: The metallic layer shall be applied over each core or applied as a collective screen. The metallic screen shall consist of either copper tapes or a concentric layer of copper wires or a combination of tapes and wires.
- Over Sheath: Overall sheath comprises a layer of extruded either PVC type 9 conforming to BS 7665-4.2 or MDPE type TS2 conforming to BS 7655-10.1. LSZH can be offered as an option.
Physical Properties
- Operating Temperature: up to 90°C
- Temperature Range: -5°C (PVC or LSZH sheath); -20°C (PE sheath)
- Short Circuit Temperature: 250°C (short circuit duration up to 5 seconds)
- Bending Radius: 12 x OD
Technical Specifications
Insulation Thickness at Nom. Voltage
Nom. Cross Section Area | Insulation Thickness at Nom. Voltage |
19/33KV(Um=36KV) | |
mm² | mm |
70 – 185 | 8.0 |
240 | 8.0 |
300 | 8.0 |
400 | 8.0 |
Above 500 | 8.0 |
Electrical Parameters
Nom.Cross-Section Area | DC Resistance CUAL | AC Resistance CUAL | ShortCircuit Rating of Conductor CUAL 1sec | Capacitance | Charging Current | Reactance | Inductance |
mm² | µΩm | µΩ/m | kA | pF/m | mA/m | µΩm | nH/m |
25 | 727/1200 | 927/1538 | 3.6/2.3 | 176 | 0.48 | 132 | 410 |
35 | 524/868 | 668/1113 | 5.0/3.2 | 193 | 0.53 | 123 | 390 |
50 | 387/641 | 494/822 | 6.8/4.4 | 211 | 0.58 | 116 | 370 |
70 | 268/443 | 343/568 | 9.8/6.3 | 240 | 0.65 | 110 | 350 |
95 | 193/320 | 248/410 | 13.3/8.5 | 267 | 0.73 | 105 | 330 |
120 | 153/253 | 196/325 | 17.2/11.0 | 291 | 0.79 | 102 | 320 |
150 | 124/206 | 159/265 | 21.2/13.5 | 312 | 0.85 | 98 | 310 |
185 | 99.1/164 | 128/211 | 26.6/17.0 | 340 | 0.93 | 95 | 300 |
240 | 75.4/125 | 98/161 | 34.9/22.3 | 375 | 1 | 91 | 290 |
300 | 60.1/100 | 80/130 | 43.8/28.0 | 411 | 1.1 | 89 | 280 |
400 | 47.0/77.8 | 64/102 | 57.3/36.6 | 454 | 1.2 | 84 | 270 |
Dimensions and Weights
Nom. Cross- Section Area | Nom. Insulation Thickness | Copper Tape Screen Area | Nom.Bedding Thickness | Nom. Armour Wire Diameter | Nom.Sheath Thickness | Approx. Overall Diameter | Approx. Weight | |
CU | AL | |||||||
mm² | mm | mm² | mm | mm | mm | mm | kg/km | |
50 | 8.0 | 6.7 | 1.8 | 3.15 | 3.4 | 79.0 | 10620 | 9680 |
70 | 8.0 | 7.1 | 1.8 | 3.15 | 3.5 | 82.5 | 11840 | 10440 |
95 | 8.0 | 7.5 | 1.9 | 3.15 | 3.6 | 86.4 | 13200 | 11350 |
120 | 8.0 | 7.9 | 2.0 | 3.15 | 3.7 | 89.9 | 14520 | 12190 |
150 | 8.0 | 8.2 | 2.0 | 3.15 | 3.8 | 93.6 | 16070 | 13280 |
185 | 8.0 | 8.6 | 2.1 | 3.15 | 3.9 | 97.3 | 17710 | 14090 |
240 | 8.0 | 9.2 | 2.2 | 3.15 | 4.1 | 103.2 | 20370 | 15460 |
300 | 8.0 | 9.7 | 2.3 | 3.15 | 4.3 | 108.2 | 22980 | 17210 |
400 | 8.0 | 10.3 | 2.4 | 3.15 | 4.5 | 116.8 | 27480 | 19450 |
Application Fields
Direct buried
Laid in cable trench
Laid along wall
Laid in cable tunnel
Packaging & Shipping
All cables will be packaged in different materials based on their outer diameter and net weight, and can be customized according to requirements