Aluminum-Copper Conductor Low Power Cable
Aluminum-Copper Conductor Low Power Cable

Aluminum-Copper Conductor Low Power Cable

Power Cable XLPE Low Voltage Underground

Aluminum-Copper Conductor XLPE Insulated Underground Power Cable

Certification Standards
ISO 9001 IEC CE
Implementation Standards
  • BS 6622
  • BS 7835 (LSZH Version)
Contact Us

Product Introduction

Construction

  • Conductor: Plain annealed copper or aluminium complying with IEC 60228/BS 6360. Copper conductors shall be stranded and aluminium conductors shall be either solid or stranded.
  • Conductor Screen: Extruded layer of semi-conducting cross-linkable compound is applied over the conductor and shall cover the surface completely. The minimum thickness is 0.3mm and the maximum resistivity shall not exceed 500 Ohm-m at 90°C.
  • Insulation: Cross-linked polyethylene compound XLPE (GP8) conforming to BS 7655-1.3 or EPR (GP7), conforming to BS 7655-1.2.
  • Insulation Screen: Extruded layer of semi-conducting cross-linkable compound is applied over the insulation. The minimum thickness is 0.3 mm and the maximum resistivity is 500 Ohm-m at 90°C.
  • Metallic Layer: The metallic layer shall be applied over each core or applied as a collective screen. The metallic screen shall consist of either copper tapes or a concentric layer of copper wires or a combination of tapes and wires.
  • Over Sheath: Overall sheath comprises a layer of extruded either PVC type 9 conforming to BS 7665-4.2 or MDPE type TS2 conforming to BS 7655-10.1. LSZH can be offered as an option.

Physical Properties

  • Operating Temperature: up to 90°C
  • Temperature Range: -5°C (PVC or LSZH sheath); -20°C (PE sheath)
  • Short Circuit Temperature: 250°C (short circuit duration up to 5 seconds)
  • Bending Radius: 12 x OD

Technical Specifications

Insulation Thickness at Nom. Voltage
Nom. Cross Section AreaInsulation Thickness at Nom. Voltage
19/33KV(Um=36KV)
mm²mm
70 – 1858.0
2408.0
3008.0
4008.0
Above 5008.0
Electrical Parameters
Nom.Cross-Section AreaDC Resistance CUALAC Resistance CUALShortCircuit Rating of Conductor CUAL 1secCapacitanceCharging CurrentReactanceInductance
mm²µΩmµΩ/mkApF/mmA/mµΩmnH/m
25727/1200927/15383.6/2.31760.48132410
35524/868668/11135.0/3.21930.53123390
50387/641494/8226.8/4.42110.58116370
70268/443343/5689.8/6.32400.65110350
95193/320248/41013.3/8.52670.73105330
120153/253196/32517.2/11.02910.79102320
150124/206159/26521.2/13.53120.8598310
18599.1/164128/21126.6/17.03400.9395300
24075.4/12598/16134.9/22.3375191290
30060.1/10080/13043.8/28.04111.189280
40047.0/77.864/10257.3/36.64541.284270
Dimensions and Weights
Nom. Cross- Section AreaNom. Insulation ThicknessCopper Tape Screen AreaNom.Bedding ThicknessNom. Armour Wire DiameterNom.Sheath ThicknessApprox. Overall DiameterApprox. Weight
CUAL
mm²mmmm²mmmmmmmmkg/km
508.06.71.83.153.479.0106209680
708.07.11.83.153.582.51184010440
958.07.51.93.153.686.41320011350
1208.07.92.03.153.789.91452012190
1508.08.22.03.153.893.61607013280
1858.08.62.13.153.997.31771014090
2408.09.22.23.154.1103.22037015460
3008.09.72.33.154.3108.22298017210
4008.010.32.43.154.5116.82748019450

Application Fields

Direct buried

Laid in cable trench

Laid along wall

Laid in cable tunnel