H05V-K / H07V-K
PVC Insulated
Copper Wire
Flexible Cable
Single Core
Multi Core
PVC Insulated Copper Wire H07V-U H05V-K H07V-R H07V-F cable
Implementation Standards
- BS EN 50525-2-31
- BS EN / IEC 60332-1-2
Product Introduction
CONSTRUCTION of H05V-K / H07V-K
- Conductor: Class 5 flexible copper conductor according to BS EN 60228 (previously BS 6360)
- Insulation: PVC (Polyvinyl Chloride) Type TI1 according to BS EN 50363
CHARACTERISTICS
- Voltage Rating (Uo/U):
- H05V-K: 300/500V
- H07V-K: 450/750V
- Temperature Rating:
- Fixed: -30°C to +70°C
- Flexed: -5°C to +70°C
- Minimum Bending Radius:
- 12: 5 x overall diameter
- 12: 6 x overall diameter
Sheath Colour
- Single Core: Brown or Blue
- Two Core: Brown and Blue
- Three Core: Brown, Blue and Green / Yellow
- Four Core: Green / Yellow, Black, Brown and Blue
- Five Core: Green / Yellow, Black, Brown, Blue and Black
Additional Information
- Sheath Colour: Grey (Other colours available to order)
- Minimum Bending Radius: 10 times
- Maximum Conductor Temperature: 70°C
- Maximum Conductor Temperature During Short Circuit: 160°C
- Cable Standards: BS EN 50525-2-31 (previously BS 6004, Cenelec HD21.3) BS EN / IEC 60332-1-2
Application of Cable H05V-K / H07V-K
- PVC panel wiring for use in the switch control, relay and instrumentation panels of power switchgear and for purposes such as internal connectors in rectifier equipment, motor starters and controllers.
Technical Specifications
Technical Specifications
Nominal voltage Uo/U | [V] | 300 / 500 volt 450 / 750 volt |
Test voltage | [V]AC | 2500 |
Temperature range | in motion | +5°C till +90°C |
Operating temperature | short circuit | 250°C |
Short circuit time | max. | 5 [sec] |
Bending radius | one time / fixed | 6 x diameter |
Flammability | standard | EN 60332-1 |
H05V-K H07V-K | IEC 60332-1 |
Application Fields
Switch control panels
Relay and instrumentation panels of power switchgear
Internal connectors in rectifier equipment
Motor starters and controllers
Packaging & Shipping
All cables will be packaged in different materials based on their outer diameter and net weight, and can be customized according to requirements